Regarding the hydro-cooling cycle system, cleaning is divided into cycle system cleaning and hydro-cooling miner cleaning. The specific descriptions are as follows.
Cycle System Cleaning
The cycle system needs to be cleaned and filtered before hydro-cooling miners are put into a cabinet.
Before connecting the cabinet to the cycle system, deionized water (conductivity ≤ 5 μs/cm) is used to clean and filter cycle system pipeline multiple times to remove dust, welding slag, and other impurities. Cleaning time should not exceed 8 hours, and cleaning liquid should not be left overnight in the cycle system. After the cycle system is cleaned, the deionized water should be drained, and then coolant is injected for cycling (if the deionized water is not completely drained, it will affect various indicators and parameters of the coolant). If there are too many residual impurities in the system, the cooling plates or connectors may easily have the risk of the corrosion and blockage, which may cause the damage to the hydro-cooling miner. We will shoulder no responsibility for such damage to the miner.
Hydro-Cooling Miner Cleaning
The hydro-cooling miner needs to be cleaned and filtered before it is put into the cabinet.
Before the hydro-cooling miner is put into the cabinet, the deionized water (conductivity ≤ 5 μs/cm) is used to clean and filter a flow channel of the hydro-cooling miner multiple times to remove the dust, remaining liquid and other impurities. The cleaning time should not exceed 8 hours, and the cleaning liquid should not be left overnight in the hydro-cooling miner. After cleaning the hydro-cooling miner, the deionized water should be drained, and then the coolant is injected for cycling (if the deionized water is not completely drained, it will affect various indicators and parameters of the coolant). If there are too many residual impurities in the hydro-cooling miner, the cooling plates or connectors may easily have the risk of the corrosion and blockage, which may cause the damage to the hydro-cooling miner. We will shoulder no responsibility for such damage to the hydro-cooling miner.