Is it feasible to arrange 140 units of M65S+ in a 1 MW mining box? From what perspective should quantity be considered?
whatsminer
2025.08.18
153
0

It is not feasible to arrange 140 units of M65S+ in a 1 MW mining box. It is best to calculate the quantity based on the power of each miner in normal mode or overclocking mode. The power of 1 unit of M65S+ in normal operation is about 7200 W or 7300 W, so the power of 140 units of M65S+ actually exceed 1 MW.